Part No.: MPHS-NT-50-CO-EN-S2P-IO-D (Slave to PROFINET IO Device)
MPHS-NT-50-CO-EN-S2P-IO-C (Slave to PROFINET IO Controller)
MPHS-NT-50-CO-EN-M2P-IO-D (Master to PROFINET IO Device)
MPHS-NT-50-CO-EN-M2EN/IP-A (Master to EtherNet/IP Adapter)
MPHS-NT-50-CO-EN-M2OM-TCP (Master to Open Modbus/TCP)
MPHS-NT-50-CO-EN-S2EN/IP-S (Slave to EtherNet/IP Scanner)
MPHS-NT-50-CO-EN-S2P-IO-C (Slave to PROFINET IO Controller)
MPHS-NT-50-CO-EN-S2EN/IP-A (Slave to EtherNet/IP Adapter)
MPHS-NT-50-CO-EN-S2OM-TCP (Slave to Open Modbus/TCP)

Gateway CANopen Slave: Cost-optimized entry level Gateway for simple conversions

產品介紹

Features

  • Integrates a single PROFINET IO Device into a CANopen network
  • Short I/O data conversion time lower than 20 ms
  • Extremely space-saving compact design
  • Loadable Firmware for flexible use of other conversions
  • With Ethernet diagnostic and configuration port

Product Description

netTAP 50 is a protocol converter for simple conversions. netTAP 50 converts 1-port Real-Time Ethernet, fieldbus and serial automation protocols. Slave to slave or slave to master conversions are supported. As a master, netTAP 50 provides full master functionality to one slave device only. This makes it easy to integrate a single field device into any higher-level network.

The design impresses with a cost-optimized, compact hardware implementation being reduced to the elementary requirements of a protocol converter. The converter addresses market segments which set the focus on cost savings. The cost-reduced design combined with its countless conversion possibilities makes netTAP 50 an attractive gateway in terms of price and universality.

 

Technical Details

Product Product Name NT 50-CO-EN
Product Part Number 1756.110
Brief Description Gateway CANopen to Ethernet
Communication Controller Communication controller: netX 50
Integrated Memory
RAM: 8 MB SDRAM
FLASH: 4 MB serial Flash
Power Supply
Supply voltage: 24 V ± 6 V DC
Current consumption at 24 V (typically): 72 mA
Connector type: Mini-COMBICON, 2-pin
Communication Interface 1
Communication interface: CANopen
Interface type: ISO 11898, optically isolated
Connector type: D-Sub male, 9-pin
Communication Interface 2
Communication interface: Ethernet
Interface type: 100 BASE-TX or 10 BASE-T, isolated
Connector type: 1 * RJ45
Diagnostic Interface
Type: Ethernet, 4-pin
Connector type: RJ45 socket
Display
Display 1: SYS System status
Display 2: APL Application status
Display 3: COM Communication status
Display 4: LINK Link, ACT Activity
Permitted Ambient Conditions
Ambient temperature (operation): 0 … +60 °C
Relative humidity (operation): no condensation allowed
Device
Dimensions (L x W x H): 100 x 26 x 66 mm (without connector)
Weight: appr. 80 g
Degree of protection: IP 20
Mounting type: on DIN rail EN 60715
Configuration Configuration software: SYCON.net
Conformity RoHS: yes  
Conformance with EMC Directives
CE sign: Yes
Emission: CISPR 11 Class A
Immunity: EN 61131-2:2003

Ordering Information 

  • NT 50-CO-EN (1756.110) - Gateway CANopen to Ethernet