NJ 100DN-DP (M/S)

Part No.: MPHS-NJ-100DN-DP+M (+Master Licence)
MPHS-NJ-100DN-DP (Slave only)

PROFIBUS DP Master/ Slave: Can be mounted at any point of the delivery chain

產品介紹

Features

  • Universal PROFIBUS interface in closed IP40 housing
  • Host connection via Dual-Port Memory
  • Master oder Slave on the same hardware
  • Easy slide-in mounting without tools
  • Locks and connects without additional components on the baseboard

Product Description

The universal communication module netJACK with its PCI Express interface addresses in particular the embedded market with high-performance CPUs like Intel Atom®. Alternatively, there are versions with a traditional dual-port memory and a fast serial SPI interface.

All types have the compact design of a closed IP 40 module which can be mounted without using tools. Additional costs for the device will not arise because connector and mounting rails are designed as contact areas and cut-outs on the baseboard.

netJACK can be mounted quickly and easily right before shipment - or even by the end customer.

With netJACK customers can realize the full range of communication solutions, e.g. for drives, HMI or ident systems. At the same time, additional functionalities as PLC, visualization or individual applications are possible. For customer-specific requirements, Hilscher offers a cost-optimized Design and Production Service.
 

Technical Details

Product Part number 1623.400
Brief Description Exchangeable Module Dual-port memory - PROFIBUS DP
Communication Controller netX: netX 100
Integrated Memory

RAM: 8 MB SDRAM
FLASH: 4 MB serial Flash EPROM

Power
Supply
and Current
Supply voltage: +3.3 V ± 5 % DC
Typical/maximum current: 434-500 mA
Typical power consumption: 1,43 W
System
Interface
Bus type: Parallel dual-port memory
Connector type: 80 pin connector, SAMTEC FSI-140-03-G-D-AB
Pin distance/pin width: 0.45 mm/0.55 mm
Dual-port-memory size: 64 KB (16 address lines), where 16 KB used by firmware (14 address lines, lowest 16 KB)
Width for the data access to the Dual-Port Memory (DPM): 8/16 bit
Communication
Interface
Communication standard (protocol): PROFIBUS
Interface type: RS-485, potential-free
Connector: D-Sub, 9-pin
Diagnostic
Interface
Type: USB or UART
Connector: Signal at host interface. Available only if integrated in host system
Display Display:
  • SYS System Status, green: RUN, yellow: RDY
  • COM Communication status, green: STA, red: ERR
Environment
Ambient temperature range for operation: -20°C … +70 °C
Ambient temperature range for storage: -10°C … +70 °C
Device Dimensions (L x W x H): Length: 68.2 mm / 60 mm (with / without DSUB socket), width: 53.4 mm (at front panel) / 50.4 mm (body), height : 25.2 mm (at front panel) / 19.2 mm (body)
Weight: approx. 68 g
Housing: Closed module
Protection class: IP40
Mounting/Installation: Via milled footprint holes in the carrier board and retaining brackets. No mounting accessories required.
Mounting/pulling cycles: max. 10
Configuration Configuration software: SYCON.net
Conformity RoHS: yes
Reach: yes
UL certification UL type: cURus
UL file: E334100
Conformance
with EMC
Directives
CE Sign: yes
 
Emission: EN55011:2009; CISPR 11, class A
 
Immunity: according to EN 61131-2:2003
 
Electrostatic discharge (ESD) according to IEC/EN61000-4-2 (Air discharge method): IEC/EN 61000-4-2:2009: ± 8 kV, Criterion A

Electrostatic discharge (ESD) according to IEC/EN 61000-4-2 (Contact discharge method): IEC/EN 61000-4-2:2009: ± 4 kV, Criterion A

Fast transient interferences (Burst), according to IEC/EN 61000-4-4: IEC/EN 61000-4-4:2004+A1:2010: ± 1.1 kV, Criterion A

Surge voltage, according to IEC/EN 61000-4-5 (Communication and data lines): IEC/EN 61000-4-5:2006: 1 kV, Criterion A
Tests Shock: EN60068-2-27 Ea
Vibration: EN60068-2-6 Fc

 

Ordering Information

  • NJ 100DN-DP/DPM (1623.400/DPM) - Exchangeable Module Dual-port memory - PROFIBUS DP Master