Part No.: MPST-ACCON-NetLink-PRO-compact
Protocol Converter for Data Exchange Between Different SIMATIC S7 Controllers
Compact PROFIBUS/MPI Adapter for Ethernet Connection of SIMATIC S7 Controllers
ACCON-NetLink-PRO compact enables simple and fast integration of SIMATIC S7-200/300/400 controllers into Ethernet networks. This enables programming, configuration, and SCADA applications such as STEP7, TIA Portal, WinCC or OPC Servers to access multiple automation devices robustly and cost-effectively in parallel. The adapter can be plugged directly into the MPI connector and replaces expensive Communication Processors. The looped-through programming device socket allows retroactive piggyback mounting.
For configuration purposes, ACCON-NetLink-PRO compact can be integrated as a programming device in the familiar STEP7 or TIA Portal development tools. In addition, a web interface is available for basic settings, e.g., the PROFIBUS subscriber address or the IP address. SIMATIC S7-200/300/400 controllers without Ethernet connection can also be connected to SIMATIC S7-1200/-1500 controllers with Ethernet connection via the adapter. ACCON-NetLink-PRO compact can be supplied with power directly via the SIMATIC S7 controller or via the 24VDC connection.

Integration of S7-200, S7-300 and S7-400 into 10/100 Mbit Ethernet Networks
Programming Adapter Supporting all Relevant S7 Engineering Tools
Application Integration through RFC1006 and OPC UA
| General Information | Supported Controllers | Siemens SIMATIC S7-200, S7-300, and S7-400 | |
|---|---|---|---|
| Housing, Dimensions (W x H x D) | 40 x 17 x 64 mm | ||
| Weight | Approx. 110 g | ||
| System Requirements | No limitation (the driver for SIMATIC NETLink-S7-NET only Windows XP, 7, 8.1, 10, 2K3 R2, 2K8 R2, 2K12 R2) | ||
| Configuration Software | Web configuration | ||
| PC Communication Interface | Number | 1 | |
| Type | Ethernet 10 Base-T, Ethernet 100 Base-TX | ||
| Connection | RJ45 | ||
| Supported Transfer Rates to PLC | 9.6 KBit/s ... 12 MBit/s with automatic detection | ||
| Supported Transfer Rates to PC | 10/100 Mbps autom. detection | ||
| Supported Bus Systems | PROFIBUS, MPI | ||
| Simultaneous Connections | 16 TCP/IP connections | ||
| Application | Number | 1 | |
| Type | RS485, isolated | ||
| Connection | SUB-D male connector, 9-pin. with PG interface and repeater | ||
| Transmission Rate | Max. 12 Mbps | ||
| Status Indicator | 5 LEDs, 2 of them bicolor | ||
| Voltage Supply | 24 VDC, 18–30 V DC | ||
| Current Draw | Max. 200 mA with 24 VDC | ||
| Simultaneous Connections | 32 MPI / PROFIBUS connections | ||
| Ambient conditions | Ambient Temperature | 0 °C ... +60°C | |
| Transport & Storage Temperature | -20 °C … +80 °C | ||
| Relative Air Humidity | 95% RH without condensation | ||
| Pollution Degree | 2 | ||
| Protection rating | IP20 | ||
| Approvals | CE | ||
| CE | CE | Yes | |
| REACH | Yes | ||
| Scope of Delivery | |
|---|---|
| Hardware | ACCON-NetLink-PRO compact gateway |
| Order Numbers | |
| 161701-PRO | ACCON-NetLink-PRO compact |
| Additional products and services | |
| 700-5596-04 | AC Adapter, 24 VDC, Euro, UK, or USA |
| SDEX Suite | |
| OPC Suite | |
Note: