Part No.: MPHS-CIFX-50-DP+M (+Master License)
MPHS-CIFX-50-DP (Slave only)
PROFIBUS DP-Master/ Slave: Communciation for PC-based Automation
The entire protocol stack is processed on the PC card. The process data exchange with the host is executed via Dual-Port-Memory or DMA (Direct Memory Access). Thanks to the uniform Hilscher platform strategy, all PC cards use the same drivers and tools, irrespective of protocol and card format. Communication protocols can be changed easily by loading the appropriate firmware. A rotary switch allows a simple and reliable slot assignment of the PCI and PCI Express card types. Moreover, special types are available, e.g. with integrated NVRAM, 2-channel cards or detached network interface.
A complete software package is always included within the scope of delivery. This package consists of an FDT-based configuration tool (IEC standard) for all products and networks, loadable firmware, documentation, and a driver tool kit.
Due to the Hilscher network controller netX, a 10-years delivery guarantee is granted.
Product | Product Name | CIFX 50-DP |
---|---|---|
General Part No. | 1250.410 | |
Brief Description | PC Card cifX PCI PROFIBUS DP Master or Slave or PROFIBUS MPI Device | |
Function | Communication interface with PCI and PROFIBUS interface | |
Communication Controller | Type: netX 100 | |
Integrated Memory |
RAM: 8 MB SDRAM |
|
System Interface |
Bus type: PCI Transmission rate: 33 MHz Data access: DPM or DMA (Direct Memory Access) Data width: 32-Bit |
|
Communication Interface |
Communication standard: PROFIBUS Interface type: RS-485, isolated Isolation voltage: 1000 V DC (tested for 1 minute) Connector: D-Sub, female, 9-pin |
|
Power Supply |
Supply voltage: +3.3 V DC ±5 % Maximum current (typically): 700 mA (at 3,3 V) Connector: via PCI Bus |
|
Displays |
LED display:
|
|
Operating Element | Rotary switch slot number (card ID): To set the slot number (card ID) | |
Permitted Ambient Conditions |
Operating temperature range: -20 °C ... +70 °C (Air flow during measurment: 0,5 m/s) Storage temperature range: -10 °C ... +70 °C Humidity: 10 % … 95 % relative humidity, no condensation permitted Environment: For UL compliant usage: The device must be used in a pollution degree 2 environment. |
|
Device |
Dimensions (L x W x H): 120,0 x 86 x 18,5 mm (from hardware revision 5) Mounting/Installation: PCI slot (3,3 V) |
|
Conformity | RoHS: Yes | |
Conformance with EMC Directives |
CE sign: Yes Emission: EN 55011: 2009 + A1:2010, CISPR 11:2009, Class A (Radio disturbance characteristics - Limits and methods of measurement) Immunity:
|
|
UL Certification |
UL: The device is certified according to UL 508 UL file: UL-File-Nr. E221530 |
|
Configuration |
Configuration software for master and Slave: SYCON.net Configuration software Slave: netX Configuration Tool |