NSCD-T52-EN/ATVISE/PN

Part No.: MPHS-NSCD-T52-EN
PROFINET PLCs: Visualizing modern, flexible and economically over the web

產品介紹

Features

  • Brings your PROFINET S7 PLC controlled machinery to the web
  • Enables platform neutral and free of charge visualization over all common browsers
  • Lets you monitor and operate your machinery from any mobile anytime, anywhere
  • Comes with touchscreen-ready controls and gadgets for fast implementation without programming

Product Description

The Web-HMI Server brings your PROFINET S7 PLC controlled automation equipment and industrial manufacturing systems to the web. The device links to the targeted PLC with the Ethernet protocol ISO on TCP (RFC1006) that is supported by any PROFINET S7 PLC. The integrated 2-port Ethernet switch on the underside connects the device IT-friendly to the existing LAN network. The independent third Ethernet port on the front connects to the PLC.

The web visualization is managing the pages without plugins such as ActiveX®, Flash® or Java®. It can be executed by all leading web browsers. The interface scales automatically and adjusts to work on any web browser enabled device from a Smartphone all the way up to a web-enabled High-definition television. The simultaneous access of multiple browsers at a time is also supported.

Although native web technology is being used no HTML code programming necessary. Front end creation as well as the dynamizations of the visualizing controls and gadgets are easily and quickly configured with a few mouse clicks. The PLC values as basis are defined as tags in a symbol editor and just applied to the controls afterwards. Color change, movement, scaling, user rights, the support of all common graphic formats and multilingualism are possible. Online data monitoring, alarming/acknowledgment and data trending are supported. For best visual effects a large catalogue of high-quality graphics from the industrial sector is available as library on demand.
 

Technical Details

Product Part Number 1880.110/ATVISE/PN
Brief Description Web-HMI Server for S7 PROFINET PLCs
Communication Controller Type: netX 52
Integrated Memory RAM: 8 MB SDRAM
Power Supply Supply voltage: 18 – 30 V DC
Current (typically): 130 mA (at 24 V), 190 mA (at 18 V), 110 mA (at 30 V)
Connector: COMBICON MC 1.5/5, 5-pin
Communication Interface 1 Communication standard: Ethernet
Interface type: 10BASE-T/100BASE-TX, isolated
Connector: 2 x RJ45 sockets
Communication Interface 2 Communication standard: Ethernet
Interface type: 10BASE-T/100BASE-TX, isolated
Connector: 1 x RJ45 sockets
Auto negotiation: supported
Auto cross over:supported
LED Indicators LEDs:
  • SYSTEM, System status  
  • CONFIG, Configuration status  
  • MODBUS Modbus status  
  • ACTIVE Visualization status  
  • LOAD, File download status  
  • ACT, Ethernet activity status  
  • LNK, Ethernet link status
Permitted Ambient Conditions Operating temperature range: 0 °C … +50 °C
Humidity:10 % … 95 % relative humidity (not condensing)
Device Dimensions (L x W x H): 88 x 22,5 x 78 mm
Weight: appr. 84 g
Protection class: IP20
Mounting: Top hat rail mounting according to DIN EN 60715
Conformity RoHS: Yes
Conformance with EMC Directives CE sign: Yes

Emission: EN 55011:2009 + A1:2010, Class A

Electrical immunity to interference: EN 61131-2:2008

Electrostatic discharge (ESD): According to IEC/EN 61000-4-2:2008: 8 kV Air discharge, Criterion B; 4 kV Contact discharge, Criterion B

Fast transient interferences (Burst): Zone B, according to IEC/EN 61000-4-4:2012: 2 kV Power supply connector DC, Criterion B; 1 kV Communication lines Ethernet, Criterion B

Surge voltage: Zone B, according to IEC/EN 61000-4-5:2006: 0.5 kV CM/DM Power supply connector DC, Criterion B; 1 kV CM Communication lines Ethernet, Criterion B
SIMATIC S7 PLC PLC types: S7-1200/1500, PROFINET S7-300/400
PLC Ethernet protocol: RFC1006, Port 102, on PROFINET
Ethernet Communication Transmission rate: 10/100 MBit/s
Connections: Min. 3 TCP connections to browser at the same time possible.
Data transport: TCP/IP
Integrated Server/Clients FTP server: RFC 959, Port 21, passive mode
HTTP server: RFC 2616, Port 80, HTTP/1.1
SNTP client: RFC 2030, Port 123, time synchronization
Integrated WebServer Supported protocol: HTTP/1.1 - Hypertext Transfer Protocol (RFC 2616)
Maximum number of sockets: Min. 3 browser connections at the same time
Supported HTTP methods: GET, HEAD, POST
atvise webMI standard: Supported
Request URI to file system mapping: Supported
Media type recognition from filename suffix: Supported
Server Side Includes (SSI): Supported
Chunked Transfer Encoding: Not supported
Version: 1.1.0
Real-time Clock Type: Hardware supported
Precision: 20 ppm
Power failure-safe: Yes
Buffering: Min. 7 days, maintenance-free by SuperCap
Synchronization: Manually or cyclically by SNTP (via 123/UDP port)
Visualization Web visualization: atvise webMI with Hilscher plug-ins
Engineering tool: atvise builder by Certec
Variables/data points: Limited by memory only: 1 KByte web applikation memory per variable
Web memory consumption:200 KByte per visualization page (typically)
Standard functions: Alarm, trend and user management
Adaptability: Entirely customizable using Java scripting
Multilingualism: Standard: german/english (can be extended)
Web application memory: 6 MB non-volatile FLASH memory
Trending Trend variables: Up to 32 Variables possible
Sampling rate: 200 ms to 24 hours
Recording time: Depending on the number of variables and the sampling rate. Example: 8 Variables @ 60 sec. sampling rate = 45 days; 18 Variables @ 60 min. sampling rate = 1200 days
Trending memory: 8 MB non-volatile FLASH memory
Web browser Supported by Atvise with Min. 3 Simultaneously Active Connections Microsoft Internet Explorer: 8 (with VML conversion), 9 and 10
Mozilla Firefox: 24
Apple Safari: 5.1.7
Google Chrome: 31
Opera: 16
Blackberry: 6 or 10

 

Ordering Information

  • NSCD-T52-EN/ATVISE/PN (1880.110/ATVISE/PN) - Web-HMI Server for S7 PROFINET PLCs