MU-Thermocouple1 CAN

Part No.: MPPK-TC1-CAN-MR-K (Measuring Range K)
MPPK-TC1-CAN-MR-J (Measuring Range J)
MPPK-TC1-CAN-MR-T (Measuring Range T)

The Thermocouple measuring unit offers connections for 8 thermoelements for different temperature ranges (J, K, T).

Product Description

Configurable System for Data Acquisition and Data Processing

The Thermocouple measuring unit offers connections for 8 thermoelements for different temperature ranges (J, K, T).

Measurement data can be preprocessed and transmitted via CAN bus using a central microcontroller. Configuration work involves using Windows® software on a computer connected to the same CAN bus.


Requirements

The configuration requires a PEAK CAN interface.


Technical Specifications

  • 8 Mini sockets for thermocouple types J, K, and T (depending on the assembly of measuring modules at delivery)
  • 4 galvanically isolated measuring modules, each with 2 thermocouple sockets of the same type
  • Measuring ranges:
    • J: -210 to +1121 °C
    • K: -200 to +1370 °C
    • T: -200 to +400 °C
  • Measurement accuracy: 0.2 %
  • Accuracy of the reference sensors: typically ±0.5 K, max. ±1.0 K at +25 °C ambient temperature
  • Resolution for temperature data at CAN communication: 1/16 °C
  • High-speed CAN connection (ISO 11898-2) for data transfer and configuring
    • Bit rates from 40 kbit/s up to 1 Mbit/s
    • Galvanic isolation up to 500 V
    • NXP TJA1040 CAN transceiver
    • Complies with CAN specifications 2.0 A/B
  • Basic configuration with the Windows® software Thermocouple Configuration
  • Advanced configuration with the Windows® software PPCAN-Editor 2
  • Preprocessing of readings possible with integrated microcontroller
  • Aluminum casing with flange. DIN rail fixing option available on request
  • Voltage supply from 6 to 34 V
  • Extended operating temperature range from -40 to 85 °C (-40 to 185 °F)

Product Includes...

  • MU-Thermocouple1 CAN in aluminum casing
  • Mating connector for voltage supply
  • Configuration software Thermocouple Configuration for Windows® 10, 8.1, 7 (32/64-bit)
  • Configuration software PPCAN-Editor 2 for Windows®
  • Manual in PDF format

Requirements

  • The configuration requires a PEAK CAN interface