CANopen - CAN Bus 之工業控制|eAutomind

wwwMicroport

 現在的位置: 首頁產品簡介

PROFIBUS Tester 4 (BC-600-PB)

(未稅)台幣定價:0
產品價格標示為"0"表示未定價,
    索取報價請按聯絡我們
PROFIBUS Tester 4 (BC-600-PB)
 

簡易規格下載

PROFIBUS Tester 4 (BC-600-PB)

未命名 2

Part No. MPSF-PB-Tools-T3

All-in-one

The PROFIBUS Tester 4 combines a signal tester, a storage oscilloscope, a protocol analyzer, and a master simulator into a single tool.

This tool is designed for use in a wide range of applications – from setup and commissioning, documentation, acceptance testing, and optimization to preventive maintenance, troubleshooting and laboratory tests. In addition, the PROFIBUS Tester 4 can be used without a notebook and is able to run comprehensive network tests in stand-alone mode.

Also Suitable for Less Experienced Users

With a single mouse click (PC mode) or a single push of a button (stand-alone mode) a user is able to initiate a full examination of a PROFIBUS network including automatic signal and protocol analysis.

A summary of all results is displayed to the user in a very intuitive manner.

In PC mode, the software package has been designed to emphasize the all-important ease-of-use aspect while at the same time preserving the more in-depth diagnostic features required by networking experts. This makes the tool ideal for both less experienced users and fieldbus specialists.

Intuitive Use and Clear Readings

The PROFIBUS Tester 4 automatically detects the baud rate or open circuit voltage immediately after connection to the PROFIBUS.

In stand-alone mode, the bus can be tested using the Live Status functionality. The PC software provides many additional features for executing, analyzing, and managing bus tests. A status bar continually shows the current bus state. Using the Network Status function, the bus can be tested with a Quick Test or a user-controlled test.

The Topology Scan feature determines the overall cable length and the cable length between slaves.

 The test results can be documented in a detailed test report. The Long-Term Trend view is used for detecting sporadic faults. In the Oscilloscope and Frame Analyzer views, experts can perform in-depth, detailed analysis. For bus and device tests with the integrated master simulator, only the baud rate needs to be specified – no configuration or parameterization is required.

Specifications

Power Supply Via External AC Adapter 100 V .. 240 VAC 50/60 Hz (Galvanically Isolated) or Direct Connection to 24 VDC ±20%, Approx. 0.5 A (Without Galvanic Isolation)
RS485 (DP) PROFIBUS D-Sub Connector, 9 Pins, Power Supply for External Bus Termination
Protocol and Frame Analysis:
PROFIBUS DP and DPV1, Automatic Baud Rate Detection 9.6 Kbit/s .. 12 Mbit/s
Signal Analysis:
PROFIBUS DP, DPV1, FMS and MPI; Signal Qality Index 0 .. 5000 Determined from Signal Waveform as well as Signal/Noise Ratio and Rise Time; Signal Sampling with 8/16 Samples per Bit
Oscillogram display:
Test Range: ±5V at 10mV Resolution (Differential), 0V...15V at 15mV Resolution (A or B to DGND); Sampling Rate: Up to 384MSamples/s; Sampled Points: 2,400 (Signal Details), 8,192 (Oscillogram Analysis)
Topology scan:
Active, Maximum Distance 230 m, Accuracy ±2 m
USB V 2.0, High Speed 480 Mbit/s, Galvanically Isolated
Trigger OUT: approx. 5 V, Active Low, Connection to Storage Oscilloscope
Internal Memory Capacity 10 Memory Locations for Quick Tests, 1 Trend Log, for 41 Days Maximum
Dimensions HxWxD: 35mm x 170mm x 110mm
Weight Test Tool, No Cable: Approximately 0.45kg; Complete Carrying Case: Approximately 3.9kg
Ambient conditions
  • Operating Temperature: 0 .. 50 °C,   Storage Temperature: -20 .. 70 °C,
  • Air Humidity: 10 .. 90% without Condensation
Conformity CE, FCC, VCCI
Operation Via Four-Line Display and Four Function Keys or via PC/Notebook.
Display Localization: DE,EN,FR,IT,PL,ES (without National Language Specific Characters)
PC Operating Software PROFIBUS Diagnostic Suite, see Separate Manual

Product Package Include

PROFIBUS Tester 4, “All-In-One” Test Tool for PROFIBUS DP Bus Physics and Communication:

  • Carrying Case,
  • Wide-Range Power Supply with European and U.S. Power Cables,
  • Connection Cable for 24VDC Direct Power Supply,
  • "Standard" D-Sub PROFIBUS Adapter Cable,
  • USB Cable,
  • Terminal Block for Trigger Input/Output,
  • User Manual,
  • PB-DIAG-SUITE
  • PC Software on CD-ROM With Getting Started Manual

PROFIBUS Tester 4 (BC-600-PB)簡易規格下載
 

最新消息| 公司簡介| 產品簡介 | 線上報價 | 經銷夥伴 | 下載 | 搜尋商品 | 聯絡我們

© 2016 標高電子股份有限公司 著作權所有,並保留一切權利。